はじめる
Ignition AI Log Assistant

Ignition AI Log Assistant

Created from 10+ years of manufacturing and industrial automation experience across food packaging, planter-part manufacturing, and Tier 1 automotive environments, with Ignition used in production-facing work over that span. The skill packages practical SCADA judgment around maintainable expressions, operator-safe behavior, troubleshooting habits, and realistic Designer/Gateway validation workflows.
#エンジニアリング#生産性#教育
評価
さらに評価が必要です
販売数
0
利用方法
ダウンロード

Ignition AI Log Assistant

Diagnose Ignition 8.1 Gateway, wrapper, Perspective, Vision, module, and diagnostic-bundle evidence with an offline assistant built for real SCADA troubleshooting. This listing focuses on pasted or exported logs, copied Gateway Diagnostic Logs, wrapper logs, support bundles, screenshots, thread dumps, module/version context, and user-provided incident details.

Tested with Ignition 8.1.53.

Built from 10+ years of manufacturing and industrial automation experience across food packaging, planter-part manufacturing, and Tier 1 automotive environments, including practical Ignition use in production-facing work.

What It Helps With

  • Triage pasted or exported Ignition Gateway logs, wrapper logs, Designer/client logs, Perspective/browser errors, screenshots, and support-bundle evidence.
  • Separate the first visible error, earliest suspicious event, most frequent repeated error, likely root cause, and follow-on noise.
  • Preserve source labels, timestamps, logger names, module/version context, thread dump clues, and confidence levels.
  • Identify missing evidence needed to confirm a diagnosis without guessing from a partial excerpt.
  • Produce operator-safe next steps for an authorized Ignition administrator to validate on the target system.

Example Prompt

Use ignition-ai-log-assistant to triage this pasted Gateway log excerpt. Incident window: 2026-06-14 09:17-09:25 CDT. Production impact: the OEE Perspective dashboard stopped updating after a project save.

[Gateway Diagnostic Logs]
2026-06-14 09:18:07.412 [ERROR] [ProjectResourceManager] Error loading project resource path=Perspective/Views/OEE/LineOverview
com.inductiveautomation.ignition.common.gson.JsonSyntaxException: Expected BEGIN_OBJECT but was STRING at path $.root.props.data
2026-06-14 09:18:08.019 [WARN] [perspective.gateway.PageModel] View load failed for /oee/line-overview session=redacted
2026-06-14 09:18:16.221 [ERROR] [GatewayScriptManager] Error executing message handler project=Plant_HMI handler=refreshOee
java.lang.NullPointerException: Cannot call getCoreResults() because dataset is null
2026-06-14 09:19:02.884 [WARN] [perspective.gateway.Session] Repeated component update failures for /oee/line-overview session=redacted

Example Output

Environment Snapshot

Ignition Gateway production logs show impact to the Perspective OEE dashboard in project Plant_HMI. Affected view: Perspective/Views/OEE/LineOverview. Affected route/session path: /oee/line-overview. Related handler: refreshOee. Session identifiers were redacted.

Evidence Window

Incident window supplied: 2026-06-14 09:17-09:25 CDT. Observed errors begin at 09:18:07.412 and continue through at least 09:19:02.884, immediately after the reported project save.

Top Findings

  1. High confidence: the first hard failure is a Perspective project resource load error for OEE/LineOverview: Expected BEGIN_OBJECT but was STRING at path $.root.props.data. This points to malformed view JSON or a property value saved in the wrong shape.
  2. Medium-high confidence: the page model warning, View load failed for /oee/line-overview, explains why the dashboard stopped rendering or updating for active sessions.
  3. Medium confidence: the refreshOee message handler null dataset error is likely downstream noise or missing defensive handling after the view/data pipeline failed.

Recommended Next Steps

Restore the last known-good version of Perspective/Views/OEE/LineOverview or compare the saved resource against source control/export history. Inspect root.props.data in the affected view and confirm it is an object where Perspective expects one, not a serialized string or pasted JSON text. Add null handling in refreshOee before calling getCoreResults().

Missing Evidence

No Ignition version, Perspective module version, gateway backup, project export diff, or Designer save history was supplied. Bug/release checking was not performed because no version/module inventory was available.

Offline Capafy Edition

This Capafy edition works from user-provided evidence such as pasted logs, exported diagnostics, copied Gateway files, screenshots, thread dumps, support bundles, module/version notes, and described behavior. It does not require live Gateway access and does not manipulate a running Gateway.

Live Gateway reads, writes, automated validation, direct system collection, or real-time Gateway control are outside this download edition and require a separate connection and authorization path.

Suggested Tags

Ignition 8.1, Gateway Logs, Diagnostics, SCADA, Automation